Cutting peak demand

Demand charges depend on how the utility measures peak power. These examples show how storage changes what a site draws from the grid.

What a demand peak is, in plain terms

A business electricity bill usually has two parts. One is how much energy you used over the month. The other is how hard you pulled at your single busiest moment, measured in kilowatts. That second part is the demand charge, and one bad afternoon sets it for the whole month.

The same moment matters even when nobody is billing for it. A site can only draw so much through the connection it has. Go past that and you are asking the utility for an upgrade, which costs money and takes time.

Storage lets the site draw a steadier amount. When demand spikes, the batteries and supercapacitors cover the difference for those minutes, then refill when things quieten down. The grid sees a flatter line.

How hybrid storage keeps grid import under a limit

Each tab is a simulated site. Storage covers whatever the site draws above its grid limit, batteries on the slow part and supercapacitors on the spikes, then both refill when demand falls.

On-site sourcesOn-site sources

Simulated siteStorage starts full and is sized from this window. Losses and auxiliary loads are left out.

Afternoon cooling peak

Chillers push the building over its demand target for most of the afternoon, and compressor starts add short spikes on top. The batteries carry the sustained excess and the supercapacitors cover the starts. Whether that lowers the bill depends on how the utility measures peak demand.

Peak site demand150%

Peak grid import100%

Read the chart as text
Simulation summary for the selected site: Commercial building
Peak site demand150%
Peak grid import100%
Largest sodium-ion discharge26%
Largest supercapacitor discharge24%
Grid import above the limitNever

Simulation report

Peak demand cut from 599 kW to 400 kW, a drop of 199 kW.

Equipment: 3 sodium-ion strings, 2 supercapacitor strings, 375 kW of power conversion, filling 7 42U bays.

Email me this report

Load shapes are modelled, not measured. 100% = Grid import limit.

Battery only or hybrid: a dispatch comparison

Both designs hold the same limit in this window. What changes is how much battery you need and how hard it works. Put in your own numbers to scale it.

Load shape: Commercial building

The chart's 100% line. The comparison scales to it.

From a recent bill. Utilities usually bill an average over 15 or 30 minutes, not the instantaneous peak.

Use the demand rate from your utility tariff.

Demand charge arithmetic

Monthly, at today's billed demand
$9,600
Monthly, with billed demand at the limit
$8,000
Monthly difference
$1,600
Twelve months at that difference
$19,200

This assumes the demand reduction you entered applies every month at the rate you entered. It excludes demand ratchets and time-of-use rules.

What each design needed in this window

  • Sodium-ion strings

    Battery only
    5
    Hybrid
    3
  • Supercapacitor strings

    Battery only
    None
    Hybrid
    2
  • Power conversion

    Battery only
    250 kW
    Hybrid
    375 kW
  • Battery power, charge or discharge

    Battery only
    199 kW
    Hybrid
    127 kW
  • Fastest battery power change

    Battery only
    4.3 kW/s
    Hybrid
    1.9 kW/s
  • Battery usable energy assumed

    Battery only
    492 kWh
    Hybrid
    295 kWh
  • Supercapacitor power

    Battery only
    None
    Hybrid
    94 kW
  • Supercapacitor usable energy assumed

    Battery only
    None
    Hybrid
    16 kWh
  • Battery charge at end of window

    Battery only
    88%
    Hybrid
    80%
  • Grid import above the limit

    Battery only
    Never
    Hybrid
    Never

36%lower battery power

55%lower battery ramp

Each design starts full. Usable energy is the larger of two things: what this window drained, plus a 30% margin for the battery and 50% for the supercapacitors, and what the power envelope allows at 2C for the battery and 240C for the supercapacitors. The battery also tops the supercapacitors back up, sharing their charge terminal. The same generator behaviour feeds both designs, so only the storage differs. Losses, temperature, aging and repeat peak days are left out, so treat this as a comparison of behaviour. Sizing your own site takes your own data.

Charge level as the simulation runs

  • Battery-only system84%
  • Hybrid: sodium-ion74%
  • Hybrid: supercapacitor100%

A short spike and a billed peak are different

A demand meter may average power over an interval such as 15 or 30 minutes. A spike lasting a few seconds barely moves that average, while a sustained load sets it. Check how your tariff defines billing demand before counting savings from short spikes. Short spikes still matter where the limit is physical: a connection agreement, a transformer or a generator.

What if storage cannot cover the peak?

Storage has a power limit and a finite amount of usable energy, and a peak can exceed either one. Grid demand then rises unless another source covers the difference or loads are reduced. A site with a firm connection limit needs a defined response for that case, such as load shedding or a generator.

Modelled load shapes scaled to your numbers. Equipment, installation and financing are not included.

Other ways to handle the same peaks
  • Do nothing

    Keep the existing setup and pay the charges under your current tariff.

  • Upgrade the grid connection

    Raises the limit instead of shaving the peak. The utility sets the cost and the lead time, which can run to years.

  • Manage the load

    Stagger equipment starts, cap charger output or shift flexible work. Often the cheapest first step, where operations allow it.

  • Battery only

    Holds the same limit. The battery has to be rated for the full spike and follow every fast swing.

  • Hybrid battery and supercapacitor

    In these examples it holds the same limit with less battery power, though that depends on the load. The supercapacitors are added equipment, so compare total cost and service life, not battery size alone.